Republic Fire provides nationwide emergency light testing and inspection services. Our factory trained technicians will perform the required testing and maintenance on emergency lights and provide you with the written records as required by law. A full discharge of each unit must be performed annually.
Routine maintenance of emergency and exit lighting is frequently overlooked until an emergency occurs. Regular maintenance is required by NFPA Standard No. 101, chapter 31, section 1.3.7
NFPA Standard No. 101-31-1.3.7
."A functional test shall be conducted on every required emergency lighting system at 30-day intervals for a minimum of 30 seconds. An annual test shall be conducted for the 1 1/2 hour duration. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction."

Testing Procedures for Emergency Lights:
- Conduct a thorough examination of the unit
- Ensure the emergency lighting equipment is in its designated place
- 90 Minute full function test
- Disconnect AC power supply to each emergency light
- Check battery and lens for sulfation
- Clean each emergency light and lens as required
- Adjust beam for proper alignment
- Place testing label on the emergency light and record in testing log
- Troubleshooting/repair may also include
- Check and adjust charging system voltage
- Check battery output voltage
- Check line voltage to remote fixtures